Appendix A: TV-VVTZC-E2 Points/Properties
Point Name/Description
Heating Demand Level – The system heat demand level received over the network.
Heat Delay – The status of the terminal heat delay.
Remaining Heat Delay – If Heat Delay is Active, this is the remaining delay time.
Calculated DCV Damper Position – If the controller is in IAQ Override mode, this is the
calculated minimum damper position that will be maintained to satisfy the mode.
Calculated Dehumidify Dmpr Position – If the controller is in Dehumidify mode, this is
the calculated minimum damper position that will be maintained to satisfy the mode.
Reset Filter Alarm – Set this to On to reset an active Filter Alarm and restart the Filter
Service Alarm Timer. After the alarm returns to normal, this automatically changes to
Off.
Occupancy Contact State - The physical state of the controller's IN-04 input.
Cooling BTU's – Current Cooling Energy being delivered to the space.
Heating BTU's – Current Heating Energy being delivered to the space.
Occupancy
BAS On/Off – Determines the occupancy state of the controller and can be set over the
network by another device or third party BAS.
Options:
Inactive – Occupancy is determined by a configured schedule.
Occupied – The controller is always in the occupied mode.
Unoccupied – The controller is always in the unoccupied mode.
NOTE If BAS On/Off is set to either Unoccupied or Occupied, the Optimal Start routine
is automatically disabled.
Schedules – The controller's occupancy status based on the local schedule.
Pushbutton Override – Active indicates if a user pushed the sensor's override button to
override the occupancy state.
Override Time Remaining – The amount of time remaining in an override period.
Occupancy Contact Status – The physical state of the controller's IN-04 input.
Global Occupancy – The System Occupancy network input's current state.
TruVu™ VVTZC-E2
Installation and Start-up Guide
122
Default/Range
R:
0 to 3
R:
Inactive/Active
R:
0 to 60 minutes
R:
0 to 100%
R:
0 to 100%
D:
Off
R:
On/Off
R:
Open/Closed
R:
0 to 99999 BTU
(0 to 99999 KJoules)
R:
0 to 99999 BTU
(0 to 99999 KJoules)
D:
Inactive
R:
Inactive
Occupied
Unoccupied
R:
Occupied/Unoccupied
R:
Off/Active
R:
0 to 480 minutes
R:
Inactive
Active Unoccupied/Stdby
D:
Unoccupied
R:
Unoccupied/Occupied