Zone Environmental Index

The i-Vu® Control System uses Environmental Index (EI) to calculate a real-time numerical EI value for a zone
based on ideal Occupied space temperature, optional relative humidity (RH) and/or CO2. Environmental Index
determines the source(s) derating the EI value by continuously evaluating Occupied zone conditions. EI Decreased
By displays the source(s) derating the EI value. The EI Space Temp Setpoint Tolerance 0.5 °F (0.28 °C) is
subtracted from Effective Heat Setpoint and is added to Effective Cool Setpoint, expanding the ideal EI
temperature sensitivity range. The EI is derated from the initial Occupied value of 100% if the space temperature
deviates from the ideal EI temperature sensitivity range.
NOTE The EI Space Temp Setpoint Tolerance does not affect the controlling space temperature Effective Heat
Setpoint or Effective Cool Setpoint.
TruVu™ VVTZC-E2
Installation and Start-up Guide
Evacuation is usually the result of a fire-life safety input at the air source
being active. The terminal fully closes its primary air damper and disables
its terminal fan, if equipped.
All terminals treat VENT mode the same as the COOL mode. For VVT
terminals, VENT modes allows for an increase in airflow. VVT terminals use
the greater of the configured Vent Damper Position or the Minimum Cooling
Damper Position as the minimum during the VENT mode.
For Series or Parallel Fan controllers when the zone terminal fan is off or for
single duct controllers: The zone's local heat has not operated for at least 5
minutes, and the SAT is more than 5 °F (2.7 °C) warmer than the space
temperature. If the terminal fan is on, the SAT must be at least 8 °F
(4.4 °C) more than the space temperature.
In all cases, Heat mode is maintained until the SAT drops 2 °F (1.1 °C)
below the space temperature.
The zone's local heat has not operated for at least 5 minutes and the SAT is
between 65 (18.3°C) and 80°F (26.6°C).
The zone's local heat has not operated for at least 5 minutes, the current
mode is not Heat or Vent, and the SAT is less than 65°F (18.3°C).