Carrier TruVu VVTZC-E2 Installation And Startup Manual page 57

Table of Contents

Advertisement

Install the actuator according to the manufacturer's instructions.
1
Wire the actuator to the controller using the diagram below.
2
NOTE For proper operation and to prevent damage to the devices, use the same polarity for the actuator's power
and the TV-VVTZC-E2's power.
Linked actuators
You can wire up to 4 of the following Belimo actuators to the TV-VVTZC-E2's analog output. Use like actuators so
that travel times and other parameters coincide.
LMX24-MFT P-10028
NMX24-MFT P-10028
AMX24-MFT P-10028
Install the actuators according to the manufacturer's instructions.
1
Wire the actuators to the controller using the diagram below.
2
Set the direction rotation switch on each actuator to CW.
3
IMPORTANT! If slaving 45° actuators, you must go to Properties > I/O Points > Hot Water Valve Max and change
scaling to 200 for the slave actuator to correctly track the primary actuator.
TruVu™ VVTZC-E2
Installation and Start-up Guide
45 in.-lb (5 Nm) actuator with 0–10 Vdc control
90 in.-lb (10 Nm) actuator with 0–10 Vdc control
180 in.-lb (20 Nm) actuator with 0–10 Vdc control