Service Configuration - Carrier VVT Zone II Installation And Startup Manual

Table of Contents

Advertisement

Service Configuration

Navigation:
i-Vu® / Field Assistant:
Point Name/Description
Terminal Type – The type of zone terminal that the controller is installed on.
Damper Size (dia.) – Used by the VVT Master to calculate the weighted average
demand. If the zone damper is round, enter its diameter. If rectangular, enter 0.
Damper Area (area) – Used by the VVT Master to calculate the weighted average
demand. If the damper is rectangular, enter its area (width x height). If the damper is
round, enter 0.
Terminal Fan Airflow – Enter the terminal fan airflow in cfm (liters/second). Used in
performance calculations only. Available only on fan-enabled terminal box.
External Actuator Enable – Enable if the controller's analog output is used for an
external high-torque or slave actuator. Enabling this setting disables the output for
Modulating Hot Water or Combination reheat functions.
Heat Type – The type of supplemental reheat that the zone controller will control. The
heat may be used with system heat, depending on the space temperature demand.
Options:
None – no heat
Modulating – ducted or baseboard modulating hot water
Two Position – two position hot water
Staged EH – ducted or baseboard electric heat
Combination – combination baseboard modulating hot water and ducted staged
electric heat
SCR Electric – modulating control for SCR-type electric heater
Ducted Heat – Determines whether the zone is using ducted heat or baseboard. If Heat
Type is Combination, set this field to Yes for ducted heat.
Number of Heat Stages – The number heat stages when the Heat Type is Staged EH.
Fan powered terminals are limited to no more than 2 stages.
Valve Type – Two Position hot water only - The hot water valve's position with no power
applied to the valve.
VVT Zone II Controller
Installation and Start-up Guide
Properties
Control Program
>
77
Appendix A: VVT Zone II Points/Properties
Configuration
Service Configuration
>
>
Default/Range
D:
Single Duct
R:
Single Duct
Parallel
Series Fan
D:
6.00 in. (15.2 cm)
R:
0 to 100.00 in./cm
D:
0 sq.in. (cm. sq.)
R:
0 to 9999 sq.in.
(cm. sq.)
D:
1000 cfm
(472 liters/second)
R:
0 to 99999 cfm
(liters/second)
D:
Disable
R:
Disable/Enable
D:
None
R:
None
Modulating
Two Position
Staged EH
Combination
SCR Electric
D:
Yes
R:
No/Yes
D:
Two stages
R:
One stage
Two stages
Three stages
D:
NC
R:
NC/NO (normally
closed/normally open)
CARRIER CORPORATION ©2019
All rights reserved