Installation and Programming Manual - СА62 Alarm Control Panel
ADDReSS 0000 - CHANGING tHe eNGINeeR CoDe
A new access code to the alarm station engineer parameters can be assigned at this address.
Note: If the 6-digit long access code is set, the combination "00" automatically will be added at the end
of all valid codes in the system.
engineer
code
The light-emitting diodes 3, 4, 5 and 6 on the keypad display light up. These go out one by one as the
new code is entered. The new code has to be entered a second time.
-
Default settings
7777
ADDReSS 0001 - HARDWARe ReSet eNABLe
Reset
Disables or enables the hardware RESET of the alarm station. Specialized service is required where
enable
the hardware ReSet is disabled and the engineer code is obscure.
The parameter status can be changed with pressing of random button of the keyboard.
No
The hardware RESET is disabled.
YeS
The hardware RESET is enabled.
Default configuration
ADDReSS 0002 - ReStoRING DeFAULt PARAMeteRS (SoFtWARe ReSet)
Default
Restoration of default settings of the station. The buttons 1, 2, 3, 4, 5, 6 are pressed in succession and
settings
confirmed with the ENTER button.
ADDReSS 0003 - ReStoRING DeFAULt MANAGeR CoDe (PARtIAL SoFtWARe ReSet)
Restoration of the default manager code. Buttons 1, 2, 3, 4, 5, 6 are pressed in succession and con-
Partial reset
firmed with the ENTER button.
The station restores the default 0000 manager user code.
ADDReSS 0010 - AUtHoRItY to ARM USING A oNe PUSH-BUttoN (QUICK ARM)
A quick Arming mode using one button, without need to enter a valid user code is assigned at this ad-
Quick ARM
dress. The assigning can be done for PARTITION A, PARTITION B or for both partitions.
enable
The parameter is activated with pressing a digit number coresponding to the partition number - 1 for
PARTITION A and 2 for PARTITION B. Next pressing of the button will deactivate the parameter.
PARtItIoN
Quick Arming of PARTITION A without legal user
A
code.
PARtItIoN
Quick Arming of PARTITION B without legal user
B
code.
Default configuration

0. eNGINeeR PARAMeteRS AND CoMMoN SettINGS

     
-
YES
-
PARTITION A, PARTITION B
Indication
LeD
LCD
1 2 (3) (4) (5) (6)
     
     
     
     
Indication
LeD
LCD
1 2 3 4 5 6
Indication
LeD
LCD
(1) (2) (3) (4) (5) (6)
Indication
LeD
LCD
(1) 2 3 4 5 6
Indication
LeD
LCD
1 (2) 3 4 5 6