7.2. General Settings Menu

This menu allows the installer to make some common settings for the Repeater panel.
The menu is accessible from access levels 2 and 3, as for the level to are introduced some restrictions.
A list with submenus is displayed after entering the installer's menu - 6. GENERAL SETTING. The currently
selected submenu is blinking. To enter into a submenu press 'ENTER'.

7.2.1 Access Codes

Attention: The access codes can be changed only from access level 3!
In this submenu the installer can change the code combinations for access to INSTALLER and
MAINTENANCE levels.
To access the ACCESS CODES submenu, enter in the installer's menu - 6. GENERAL SETTING - 6.1)
ACCESS CODES.
The screen displays the supported submenus and the current set access code for the INSTALLER and
MAINTENANCE programming menus:
If the installer's access code is changed and obscured you have to perform a hardware
reset of the panel settings!
The settings are analogical for both levels.
Use the functional buttons to set access code
for:
(1) - Press to change INSTALLER CODE
(2) - Press to change MAINTENANCE CODE
(3) - Press to enter a submenu for setting time
for automatic exit from the INSTALLER and
MAINTENANCE menus.
Use the functional buttons to enter new 4-digit
INSTALLER code combination. The system will
ask to confirm the change. The exit is automatic
to Access Level main screen.
The default INSTALLER code is 3333.
Use the functional buttons to enter new 4-digit
MAINTENANCE code combination. The system
will ask to confirm the change. The exit is
automatic to Access Level main screen.
The default MAINTENANCE code is 2222.
In field „AFTER" enter time from 0 up to 60
minutes for automatic exit from the
INSTALLER and MAINTENANCE programming
menus.
Use button (4) CHANGE to set the status:
- ENABLED – The automatic exit is enabled.
- DISABLED – The automatic exit is disabled.