2.7.2 Connecting of Proxi Reader PR62 to CA62 Alarm Control Panel

The PR62 proximity card reader was designed to control security in the systems integrated within the CA62 Control
Panel. The excellent card reading distance, the triple color indications, supplemented by the sound indicator, the inte-
grated output, as well as the fine design, all make the PR62 any attractive supplement to the security system.
The PR62 can be connected to the terminals RED, GREEN, YELLOW and BLACK of the CA62 together with the
mounted keyboards. Up to four proximity readers can be included within one security system. Programming the various
addresses onto the readers will provide identification by the TAMPER of each of these. The Table for Address Program-
ming is provided on Figure 11.
The proximity-card enables to arm and disarm the system, as well as to control the electric lock (key-switch) via inte-
grated output. The internal structure, and the permissible output currents, are provided in Fig. 11.
It is possible that only proximity-card readers be included in a system without having an installed keyboard. In such
systems this would hinder current programming of parameters and cards, as well as Log Review and Technical Trouble
indications. Portable LED or LCD type keyboards can be used to accomplish such tasks.
Up to 24 cards can be assigned to one security system - one card for each of the 20 users and 4 cards for the Managers
in the system.
The Managers in the system are allowed to program the performance of the cards.
Arming and/or disarming rights must be assigned for the respective user code.
The user may not be designated a code combination. In such case the only means to control the security system would
be the proximity-card.
The parameters of the proximity card readers in the system can be programmed at ADDRESSES 71хх, according to the
set with jumper address of the proxi reader.
LED indication:
- green - the card is recognized or
required action is done,
- red - the card is not recognized or
required action is rejected,
- yellow (LED blinks) - ready.
Setting the address of PR62
Address
1
Jumper
J1
J2
Legend:
- The jumper is removed;
- The jumper is set
Figure 11. PR62 Proximity card reader installation and connection diagram.
Installation and Programming Manual - СА62 Alarm Control Panel
* The JT jumper must be set in
the most far unit on the bus.
2
3
4
Two color LED indicator
Lock
Mounting openings
Internal structure of built-in PGM
PGMx terminal
Permissable currents:
- from +12 V - up to 10 mA
- towards GND - up to 100 mA
The output activates for 2
seconds after the recognised
card is drown back.