6.1 Set Alarm Input
Set the parameters for alarm input, including trigger level, arming schedule, alarm linkage actions,
etc.
Before You Start
Connect an alarm device to your recorder.
Steps
1. Go to Menu → Others → Alarm .
2. Select Alarm Type as Alarm In.
3. Select Input No. according to actual situation.
4. Enter Alarm Name.
5. Select Trigger Level.
Note
Alarm is triggered by level. The DC range of Low Level is from 0 V to 5 V and the DC range of
High Level is from 6 V to 36 V. To avoid misinformation caused by voltage fluctuation, DC ranges
from 5 V to 6 V will not be processed.
6. Check Linkage Actions, and set the actions. For details, refer to "Set Linkage Actions".
7. Optional: Select the alarm input channel in Copy to and select Copy to copy above settings to
the selected channel.
8. Select OK.
Mobile Enforcement System User Manual
Chapter 6 Alarm Settings
Figure 6-1 Set Alarm Input
21