2: Sbus Bandwidth Considerations; Telephone Connection - Honeywell 6820 Manual

Addressable fire alarm conrol panel
Table of Contents

Advertisement

Telephone Connection

Figure 4.42 shows all possible DIP switch positions and their correlation to a numerical ID. For example, to select ID 2, place DIP switch 2
in the up or on position.
ON
OFF
Refer to Section 8.2 to edit, add, delete, and view module list.
4.15.2 SBUS Bandwidth Considerations
Each SBUS device generates a certain amount of traffic on the SBUS. Generally, the amount of traffic generated depends on the type of
SBUS device. To help you figure out the SBUS bandwidth usage of a given collection of devices, a tool is available on the Silent Knight
website (www.silentknight.com). The tool will serve as a guide to help determine how heavily loaded an SBUS is with respect to bandwidth.
We recommend you use this tool if you plan to have more than eight SBUS devices per SBUS. Remember to include devices that are on
5895XL SBUS repeaters in your list of devices for SBUS bandwidth calculations. Refer to Section 4.6.1.
4.16 Telephone Connection
Connect the telephone lines as shown in Figure 4.43. The 7860 phone cord is available from Silent Knight for this purpose. If you do not use
the model 7860 to connect to the phone lines, the wire used for the connection must be 26 AWG or larger diameter wire.
A number of programmable options are available for customizing telephone lines. These options are described in "Phone Lines" on
page 104.
6820/EVS Manual — P/N LS10144-001SK-E:E 4/6/2022
address
1
2 3
4 5 6
1
2 3
Figure 4.42 Possible SBUS Module Addresses
-
+
-
OUT-
OUT+
IN-
IN+
BATTERY
SLC
SLC PGM
Figure 4.43 Connection of Telephone Lines
address
4 5 6
1
2 3
4 5 6
DATA
VOICE
RING1
TIP1
RING1
TIP1
+
NETWORK
NETWORK
TELCO
PHONE
Model
#7860
address
1
2 3
4 5 6
RING2
TIP2
RING2
TIP2
EXT. COMM
TELCO
PHONE
supervised
Model
#7860
Control Panel Installation
address
49

Advertisement

Table of Contents
loading

This manual is also suitable for:

6820evs

Table of Contents