Control Panel Installation

4.8 Configuring Modules

This section describes how to configure any system hardware modules that have been added to the system.
4.8.1 Assigning Module IDs
When you install a hardware module (see Table 4.4 for list of compatible SBUS devices), you must use the DIP switches on the module
to assign an ID# to the module. Figure 4.21 shows all possible DIP switch positions and their correlation to a numerical ID. For example,
to select ID 2, place DIP switch 2 in the Up position.
Refer to Section Section 7.2 to edit, add, delete, and view the Module List.

4.9 Telephone Connection

Connect the telephone lines as shown in Figure 4.22. The Model 7860 phone cord is available from Honeywell for this purpose.
A number of programmable options are available so that you can customize the telephone lines. These options are described in Section
7.6.
28
Figure 4.21 Possible Module Addresses
Figure 4.22 Connection of Telephone Lines
GWF-7075 Addressable Fire Alarm Control Panel Manual — P/N LS10147-002GF-E:E 06/11/2019