UNDERSTANDING UPS OPERATION
E1, E2, E3
Input Breaker
(CB1)
(optional)
Input
Contactor
(K1)
Rectifier
Fuse
Fuse
Fuse
Inverter
Output
Contactor
(K3)
Battery
Converter
Fuse
Battery Contactor (K2)
FI-UPM
A
B
C
NOTE Callout letters
,
,
, and
Figure 6‐7. One UPM, Common Rectifier Feed, Separate Battery, Dual‐Feed Configuration, Continuous Static Switch, FI-UPM
6-12
Eaton Power Xpert 9395P UPS (300 kVA, 300 kW) Installation and Operation Manual
AC Input to
AC Input to
Bypass
UPS Rectifier
3 Wire A-B-C
3 Wire A-B-C
Rotation
Rotation
A
B
E6, E7, E8
Single-Feed Kit
Fuse
(Not supplied
with the UPS)
E4, E5
C
BATTERY CABINET
or BATTERY STRING
(Not supplied with the UPS)
D
map to Table 3‐5 on page 3-9 .
Battery Aux
48V Battery
Shunt Trip
Remote EPO
Static
Switch
Backfeed
Contactor (K5)
Fuse
Battery
Converter
Fuse
Battery Contactor (K2)
UPM 1
E4, E5
C
Battery
Battery
Breaker
Breaker
BATTERY CABINET
or BATTERY STRING
(Not supplied with the UPS)
S
P-164000563 Rev 1 www.eaton.com/powerquality
Building Alarms
Interface Board
Input
Contactor
(K1)
Rectifier
Fuse
Fuse
Inverter
Output
Contactor
(K3)
E9, E10, E11
D
UPS
CABINET
Alarm Relays
X-Slot
Interface
AC Output to
Critical Load