Eaton Power Xpert 9395P UPS (300 kVA, 300 kW) Installation and Operation Manual
Understanding UPS Operation
The Eaton 9395P UPS is a continuous-duty, solid‐state, transformerless (at 480 Vac),
three-phase, true online system that provides conditioned and uninterruptible AC
power to the UPS system's output and critical load.
The basic system consists of a rectifier, battery converter, inverter,
monitoring/operation control panel, integrated communication server, and digital
signal processor (DSP) logic. Figure 6‐1 shows the main elements of the UPS system.
If utility power is interrupted or falls outside the parameters specified in Chapter 10,
"Product Specifications," the UPS uses a backup battery supply to maintain power to
the critical load for a specified period of time or until the utility power returns. For
extended power outages, the UPS system allows you to either transfer to an
alternative power system (such as a generator) or shut down your critical load in an
orderly manner.
Battery System
Input
Input
CB1
Contactor
K1
Rectifier
Figure 6‐1. Main Elements of the UPS System
The emergency bypass consists of a continuous static switch, and a backfeed
protection contactor K5. The bypass breaker (if installed) is located in parallel with the
static switch. The backfeed protection contactor is located in series with the static
switch. The static switch is armed and ready during normal operation.
Battery
Battery
Breaker
Battery
Contactor
K2
Battery
Converter
Inverter
Power Module
Digital
Metering
Backfeed
Protection
Contactor
K5
Static
Switch
UPS Cabinet
S
P-164000563 Rev 1 www.eaton.com/powerquality
Output
Contactor
K3
AC Output
to Critical
Load
6-1