Figure 5-6. Distributed Bypass Pull-Chain Wiring With Mobs - Eaton CA22106060000R6 Installation And Operation Manual

High performance 300 kva, 300 kw for use with single upm (200–300 kva) and plus 1 (200–300 kva) ups models
Table of Contents

Advertisement

Shielded Twisted Pair
UPS 1
CAN Bridge Card J3
MOB 1
AUX 1
AUX 2
TB1
7
8
9
10
TB2
1
2
3
4
5
6
7
8
9
10
UPS 1
NOTE NC and NO designations on MOB AUX contacts are defined with breaker in OFF (open) position.
NOTE If MOB contacts have pigtail leads, use the same wire gauge to connect to UPS and use the correct crimp connections for the wire gauge.
NOTE External CAN connections between UPS cabinets require shielded twisted pair wire.
NOTE Use twisted pair wiring between the UPS and MOB AUX contacts.
NOTE Always confirm contact operation prior to wiring.
Eaton Power Xpert 9395P UPS (300 kVA, 300 kW) Installation and Operation Manual
Shielded Twisted Pair
Twisted Pair
Twisted Pair
UPS 2
CAN Bridge Card J3
MOB 2
NC
NC
COM
AUX 1
NO
NO
NC
NC
COM
AUX 2
NO
NO
TB1
7
8
9
10
TB2
1
2
3
4
5
6
7
8
9
10
UPS 2
Figure 5‐6. Distributed Bypass Pull-Chain Wiring with MOBs
INSTALLING OPTIONS AND ACCESSORIES
Shielded Twisted Pair
Twisted Pair
UPS 3
CAN Bridge Card J3
(If Installed)
Customer-Supplied Tie Cabinet
MOB 3
NC
COM
AUX 1
NO
NC
COM
AUX 2
NO
TB1
7
8
9
10
TB2
1
2
3
4
5
6
7
8
9
10
UPS 3
(If Installed)
S
P-164000563 Rev 1 www.eaton.com/powerquality
Twisted Pair
UPS 4
CAN Bridge Card J3
(If Installed)
MOB 4
NC
COM
COM
AUX 1
NO
NC
COM
COM
AUX 2
NO
TB1
7
8
9
10
TB2
1
2
3
4
5
6
7
8
9
10
UPS 4
(If Installed)
5-7

Advertisement

Table of Contents
loading

This manual is also suitable for:

9395pPower xpert 9395