Protection Against Solid Foreign Objects, Electric Shock And Water; Basic Prescriptions And Standards; Electromagnetic Compatibility - Emc - Siemens 8BT2 Installation And Operating Instructions Manual

Extendable truck- type circuit-breaker switchgear
Table of Contents

Advertisement

"Z-detail"
Fig2. Wall opening for the transfer of hot gas pressure to the outside (from the lateral of the switchgear)
2.1.5.

Protection against solid foreign objects, electric shock and water

2.1.6.

Basic prescriptions and standards

2.1.7.

Electromagnetic compatibility - EMC

881-4027.9 * INSTALLATION AND OPERATING INSTRUCTIONS 8BT2 * Revision 04
To make this arrangement on the wall, the reference point is the aisle at the front of the
switchgear (
1500mm or
side of the switchgear (X dimension) determines the length of the outlet channel. It should be
specified during the order stage to be able to provide adequate channel.
NOTE!
Please see on page49 – 54 for the detailed information of the assembly of pressure relief
channels.
8BT2 switchgear complies with the following degrees of protection according to IEC 60529:
• IP4X for switchgear enclosure of the operating front and the side walls
• IP2X for between compartments
Degree of
Type of protection
protection
IP4X
Protection against solid foreign objects: Protected against solid foreign objects, diameter > 1 mm.
Protection against electric shock: Protected against access to hazardous parts with a wire (the access probe
of 1 mm diameter shall not penetrate).
IP2X
Protection against solid foreign objects: Protected against solid foreign objects, diameter > 12.5 mm.
Protection against electric shock: Protected against access to hazardous parts with a finger (the jointed test
finger of 12 mm diameter, 80 mm length, shall have adequate clearance from hazardous parts).
Switchgear
Switching devices
Voltage detecting systems
Insulation
Surge arresters
Degree of protection
Instrument transformers
Installation, erection
Environmental conditions
To achieve appropriate electromagnetic compatibility (EMC), some basic requirements
must be observed while erecting the switchgear. This applies especially to the
installation and connection of external cables and wires.
Basic measures for ensuring EMC are already taken during design and assembly of the
switchgear panels. Among other things, these measures include:
• the low-voltage compartment is an integral part of the panel, which means that the
protection and control devices with the internal wiring are metal-enclosed;
Pressure relief flaps
2241mm dimension) as shown on fig2. The aisle at the lateral
Circuit-breakers
Disconnectors / Earthing switches
Current transformers
Voltage transformers
IEC/EN Standard VDE Standard
62271-1
0670-1
62271-200
0671-200
62271-100
0671-100
62271-102
0671-102
61243-5
0682-415
60071-1
0111
60099
0675
60529
0470-1
60044-1
0414-1
60044-2
0414-2
61936-1
0101
60721-3-3
DIN EN 60721-3-3
11