INSTALLATION

1.7 Liability Limitation

Any product damage or property loss caused by the following conditions AlphaESS
does not assume any direct or indirect liability.
• Product modified, design changed or parts replaced without AlphaESS
authorization;
• Changes, or attempted repairs and erasing of series number or seals by non
AlphaESS technician;
• System design and installation are not in compliance with standards and
regulations;
• Failure to comply with the local safety regulations (VDE for DE, SAA for AU);
• Transport damage (including painting scratch caused by rubbing inside
packaging during shipping). A claim should be made directly to shipping or
insurance company in this case as soon as the container/packaging is unloaded
and such damage is identified;
• Failure to follow any/all of the user manual, the installation guide and the
maintenance regulations;
• Improper use or misuse of the device;
• Insufficient ventilation of the device;
• The maintenance procedures relating to the product have not been followed to
an acceptable standard;
• Force majeure (violent or stormy weather, lightning, overvoltage, fire etc.);
• Damages caused by any external factors.
02
INSTALLATION
This manual introduces the basic steps of how to install and set up AlphaESS SMILE5.
SMILE5-BAT is a sealed component with no access to battery terminals or cell
components within the module.
NOTE:
please pay attention for unpacking the battery, otherwise components could be damaged.
Observe the specified minimum distances to neighboring objects.
The minimum distances ensure that:
• There is sufficient heat dissipation,
• The storage system outer cover can be opened easily,
• There is sufficient space for carrying out maintenance work.
10
11
Figure 8 Limit Distance of Installation to Neighboring Objects

2.1 Installation Site and Environment

2.1.1 General

This SMILE5 energy storage system is an indoor system and can only be installed in
an indoor location.
When SMILE5 systems are installed in a room, SMILE5 must not be hampered by the
structure of the building, the furnishings and equipment of the room.
The SMILE5 is naturally ventilated. The location should therefore be clean, dry and
adequately ventilated. The mounting location must allow free access to the unit for
installation and maintenance purposes, and the system panels must not be blocked.
The following location are not allowed for installation:
• habitable rooms;
• sites where the freezing point is reached, such as garages, carports or other places;
• sites with humidity and condensation over 85%;
• sites which are salty and where humid air can penetrate;
• earthquake areas –additional security measures are required here;
• sites that are higher than 3000 meters above the sea level;
• sites with explosive atmosphere;
• sites with direct sunlight;
• sites with extreme change of ambient temperature;
• wet rooms;
• sites with highly flammable materials or gases; or
• sites with a potentially explosive atmosphere
30cm