Liability Limitation; Installation; Installation Site And Environment - Alpha ESS SMILE5 AU Installation, Operation & Maintenance Manual

Energy storage system (ess)
Table of Contents

Advertisement

INTRODUCTION
Figure 7 Cable Box Part without Covers - Bottom View
Figure 8 Cable Box Part without Covers - left View
Object
Description
PV1, PV2
PV Connector
BAT +, BAT -
Battery Connector

1.7 Liability Limitation

Any product damage or property loss caused by the following conditions AlphaESS does
not assume any direct or indirect liability.
• Product modified, design changed or parts replaced without AlphaESS authorization;
• Changes, or attempted repairs and erasing of series number or seals by non
AlphaESS technician;
• System design and installation are not in compliance with standards and regulations;
• Failure to comply with the local safety regulations (VDE for DE, SAA for AU);
• Transport damage (including painting scratch caused by rubbing inside packaging
during shipping). A claim should be made directly to shipping or insurance company
in this case as soon as the container/packaging is unloaded and such damage is
identified;
• Failure to follow any/all of the user manual, the installation guide and the
maintenance regulations;
• Improper use or misuse of the device;
• Insufficient ventilation of the device;
• The maintenance procedures relating to the product have not been followed to an
acceptable standard;
• Force majeure (violent or stormy weather, lightning, overvoltage, fire etc.);
• Damages caused by any external factors.
Item
Description
GRID
Terminal Board Grid
Terminal Board
BACKUP
Backup Load
09
10
02

INSTALLATION

This Manual introduces the basic steps to install and set up AlphaESS SMILE5.
SMILE5-BAT is a sealed component with no access to battery terminals or cell
components within the module.
SMILE5-BAT contains a Bi-pole DC isolator, which conforms to IEC 60947. It has been
operated in all live conductors
NOTE:
Please be cautious unpacking the battery, otherwise components could be damaged.
The Smile 5 INV only compatible withAlpha LFP battery.

2.1 Installation Site and Environment

2.1.1 General
This SMILE5 energy storage system is outdoor version and can be installed in an outdoor
or an indoor location.
When SMILE5 systems are installed in a room, SMILE5 must not be hampered by the
structure of the building, the furnishings and equipment of the room.
The SMILE5 is naturally ventilated. The location should therefore be clean, dry and
adequately ventilated. The mounting location must allow free access to the unit for
installation and maintenance purposes, and the system panels must not be blocked.
The following location are not allowed for installation:
• habitable rooms;
• ceiling cavities or wall cavities;
• on roofs that are not specifically considered suitable;
• access / exit areas or under stairs / access walkways;
• where the freezing point can be reached, such as garages, carports or other places
as well as wet rooms (environmental category 2);
• locations with humidity and condensation over 85%;
• places where salty and humid air can penetrate;
• seismic areas - additional security measures are required;
• sites higher than 3000 meters above sea level;
• places with an explosive atmosphere;
• locations with direct sunlight or a large change in the ambient temperature;
• places with flammable materials or gases or an explosive atmosphere.
2.1.2 Restricted Locations
The SMILE5 shall not be installed —
(a) in restricted locations as defined for panels in AS / NZS 3000;
(b) within 600 mm of any heat source, such as hot water unit, gas heater, air conditioning
unit or any other appliance.
(c) within 600 mm of any exit;
(d) within 600 mm of any window or ventilation opening;
(e) within 900 mm of access to 240 Vac connections; and
(f) within 600 mm of side of other device.