FineSyncSource can have the following values:
Off
SPA
LON
BIN (Binary Minute Pulse)
GPS
GPS+SPA
GPS+LON
GPS+BIN
SNTP
GPS+SNTP
IRIG-B
GPS+IRIG-B
PPS
CoarseSyncSrc which can have the following values:
Off
SPA
LON
DNP
IEC 60870-5-103
The function input to be used for minute-pulse synchronization is called BININPUT. For a
description of the BININPUT settings, see the
The system time can be set manually, either via the local HMI or via any of the communication
ports. The time synchronization fine tunes the clock (seconds and milliseconds).
The parameter
synchronization within a Substation Automation System, for IEDs connected in a
communication network (IEC 61850-8-1). The
Off
SNTP -Server
IEEE 1588 (PTP)
Precision Time Protocol (PTP) is enabled/disabled using the Ethernet configuration tool /ECT)
in PCM600.
PTP can be set to On , Off or Slave only . When set to Slave only the IED is connected to the PTP-
group and will synchronize to the grandmaster but cannot function as the grandmaster.
A PTP-group is set up by connecting the IEDs to a network and enabling PTP. To set one IED as
the grandmaster change Priority2 to 127 instead of the default 128.
Busbar protection REB670
Application manual
SyncMaster defines if the IED is a master, or not a master for time
Set the course time synchronizing source (
time synchronization of line differential function is used. Set the fine time
synchronization source (
complete time synchronization. GPS alone shall synchronize the analogue
values in such systems.
Technical Manual .
SyncMaster can have the following values:
CoarseSyncSrc ) to Off when GPS
FineSyncSource ) to GPS . The GPS will thus provide the