1MRK 505 370-UEN D
Section 14
14.1
Measurement
14.1.1
Identification
Function description
Power system measurements
Phase current measurement
Phase-phase voltage measurement
Current sequence component
measurement
Voltage sequence component
measurement
Phase-neutral voltage measurement
14.1.2
Application
Measurement functions are used for power system measurement, supervision and reporting
to the local HMI, monitoring tool within PCM600 or to station level for example, via IEC 61850.
The possibility to continuously monitor measured values of active power, reactive power,
currents, voltages, frequency, power factor etc. is vital for efficient production, transmission
and distribution of electrical energy. It provides to the system operator fast and easy overview
of the present status of the power system. Additionally, it can be used during testing and
commissioning of protection and control IEDs in order to verify proper operation and
connection of instrument transformers (CTs and VTs). During normal service by periodic
comparison of the measured value from the IED with other independent meters the proper
operation of the IED analog measurement chain can be verified. Finally, it can be used to verify
proper direction orientation for distance or directional overcurrent protection function.
Busbar protection REB670
Application manual
Monitoring
IEC 61850
identification
CVMMXN
CMMXU
VMMXU
CMSQI
VMSQI
VNMMXU
GUID-9D2D47A0-FE62-4FE3-82EE-034BED82682A v1
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
P, Q, S, I, U, f
SYMBOL-RR V1 EN-US
-
I
SYMBOL-SS V1 EN-US
-
U
SYMBOL-UU V1 EN-US
-
I1, I2, I0
SYMBOL-VV V1 EN-US
-
U1, U2, U0
SYMBOL-TT V1 EN-US
-
U
SYMBOL-UU V1 EN-US
Section 14
Monitoring
SEMOD56123-2 v8
SEMOD54488-4 v12