ABB REB670 Series Applications Manual page 339

Table of Contents

Advertisement

1MRK 505 370-UEN D
12.7.3
Setting guidelines
The function does not have any parameters available in the local HMI or PCM600.
12.8
Single point generic control 8 signals SPC8GAPC
12.8.1
Identification
Function description
Single point generic control 8 signals
12.8.2
Application
The Single point generic control 8 signals (SPC8GAPC) function block is a collection of 8 single
point commands that can be used for direct commands for example reset of LED's or putting
IED in "ChangeLock" state from remote. In this way, simple commands can be sent directly to
the IED outputs, without confirmation. Confirmation (status) of the result of the commands is
supposed to be achieved by other means, such as binary inputs and SPGAPC function blocks.
12.8.3
Setting guidelines
The parameters for the single point generic control 8 signals (SPC8GAPC) function are set via
the local HMI or PCM600.
Operation : turning the function operation On / Off .
There are two settings for every command output (totally 8):
PulseModex : decides if the command signal for output x is Latched (steady) or Pulsed .
tPulsex : if PulseModex is set to Pulsed , then tPulsex will set the length of the pulse (in
seconds).
12.9
AutomationBits, command function for DNP3.0
AUTOBITS
Busbar protection REB670
Application manual
IEC 61850
identification
SPC8GAPC
PSTO is the universal operator place selector for all control functions. Even if
PSTO can be configured to allow LOCAL or ALL operator positions, the only
functional position usable with the SPC8GAPC function block is REMOTE.
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
Section 12
Control
SEMOD55398-5 v5
SEMOD176448-1 v3
SEMOD176456-2 v3
SEMOD176511-4 v7
SEMOD176518-4 v7
SEMOD158589-1 v3
333