ABB REB670 Series Applications Manual page 352

Table of Contents

Advertisement

Section 13
Logic
The equation above also implies that each individual binary output corresponds actually to one
integer, which is presented in the input ZONCONI and can be defined by:
CZ ×2
6
or
Refer to Table
Table 47:
Output names
ZONE1
ZONE2
ZONE3
ZONE4
ZONE5
ZONE6
CZ
Figure
194
connection information from one bay, say feeder 01, to a disturbance recorder in ACT for any
six-zone busbar differential protection application.
IEC16000075 V1 EN-US
Figure 194: BCTZCONN connection example
13.11
Integer to Boolean 16 conversion with logic node
representation ITBGAPC
13.11.1
Identification
Function description
Integer to boolean 16 conversion
with logic node representation
346
ZONEx ×2
x-1
, (1≤x≤6).
47
for the description of such representations.
Integer representations for the binary outputs of BCTZCONN
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
shows an example how to use BCTZCONN to facilitate the recording of the zone
Description
Bay is connected to Z1
Bay is connected to Z2
Bay is connected to Z3
Bay is connected to Z4
Bay is connected to Z5
Bay is connected to Z6
Supervision status of the check zone
on differential zones (Valid only for
feeder bays)
IEC16000075-1-en.vsdx
IEC 61850
IEC 60617
identification
identification
ITBGAPC
1MRK 505 370-UEN D
Corresponding integer value
in ZONCONI
When
deactivated
0
0
0
0
0
0
0
ANSI/IEEE C37.2
device number
-
-
Busbar protection REB670
Application manual
When
activated
1
2
4
8
16
32
64
SEMOD158419-1 v3
SEMOD167944-2 v4