Section 17
Station communication
Using PTP for synchronizing the MU
IEC17000040 V1 EN-US
Figure 215: Setting example with PTP synchronization
Settings on the local HMI under Main menu/Configuration/Time/Synchronization/
TIMESYNCHGEN:1/IEC61850-9-2:
HwSyncSrc : is not used as the SW-time and HW-time are connected with each other due to
PTP
SyncLostMode : set to Block to block protection functions if time synchronization is lost
or set to
common synchronization is lost
SyncAccLevel : can be set to 1μs since this corresponds to a maximum phase angle error of
0.018 degrees at 50Hz
Settings on the local HMI under Main menu/Configuration/Communication/Ethernet
configuration/Access point/AP_X:
Operation: On
PTP: On
Two status monitoring signals can be:
SYNCH signal on the MUx function block indicates that protection functions are blocked
due to loss of internal time synchronization to the IED
MUSYNCH signal on the MUx function block monitors the synchronization flag
in the datastream and IED hardware time synchronization.
404
IED
9-2
SAM600 TS
SAM600 VT
BlockOnLostUTC if the protection functions are to be blocked when global
PTP
SAM600 CT
IEC17000040-1-en.vsdx
1MRK 505 370-UEN D
smpSynch
Busbar protection REB670
Application manual