Section 7
Current protection
Table 35:
Setting summary for FunctionMode, StartMode and RetripMode
No.
StartMode
FunctionMode = Current
1
LatchedStart
2
LatchedStart
3
LatchedStart
4
FollowStart
5
FollowStart
6
FollowStart
7
FollowStart&
Mode
8
FollowStart&
Mode
9
FollowStart&
Mode
No.
StartMode
FunctionMode = CB Pos
10
LatchedStart
11
LatchedStart
Table continues on next page
188
RetripMode
t1 and t2
initiated with
Off
external START
UseFunction
external START
Mode
Always
external START
Off
external START
UseFunction
external START
Mode
Always
external START
Off
external START
and current
above set level
UseFunction
external START
Mode
and current
above set level
Always
external START
and current
above set level
RetripMode
t1 and t2
initiated with
Off
external START
UseFunction
external START
Mode
When t1 has
When t2 has elapsed,
elapsed, TRRET will
TRBU will be given if
never be given
current is above set
level of IPh>
be given if current
current is above set
is above set level
level of IPh>
of IPh>
always be given
current is above set
level of IPh>
never be given
current is above set
level of IPh>
be given if current
current is above set
is above set level
level of IPh>
of IPh>
be given if
current is above set
external START is
level of IPh>
present
never be given
current is above set
level of IPh> and
external START
present
be given if current
current is above set
is above set level
level of IPh> and
of IPh> and
external START
external START is
present
present
be given if
current is above set
external START is
level of IPh> and
present
external START
present
When t1 has
When t2 has
elapsed, TRRET will
elapsed, TRBU will
be given if
never be given
CBCLD input has
logical value one
be given if CBCLD
CBCLD input has
input has logical
logical value one
value one
1MRK 505 370-UEN D
GUID-B5D9E7FE-5805-47A8-B290-08E0EE76D5EB v1
t1 and t2 will be
stopped (reset) if
t1 and (t2 or t2MPh)
and 150ms expires
and current is
below set level of
IPh>
t1 and (t2 or t2MPh)
and 150ms expires
and current is
below set level of
IPh>
t1 and (t2 or t2MPh)
and 150ms expires
and current is
below set level of
IPh>
external START
disappears
external START
disappears
external START
disappears
current is below set
level of IPh> or
external START
disappears
current is below set
level of IPh> or
external START
disappears
current is below set
level of IPh> or
external START
disappears
t1 and t2 will be
stopped
(reset) if
t1 and (t2 or t2MPh)
and 150ms expires
and CBCLD input
has logical value
zero
t1 and (t2 or t2MPh)
and 150ms expires
and CBCLD input
has logical value
zero
Busbar protection REB670
Application manual