Section 12
Control
ARMode = 1ph+1*2ph, 1-phase or 2-phase reclosing in the first shot
12.2.2.11
At single-phase tripping, the operation is as in the above described example, program mode
1/2/3ph . The single-phase auto reclosing attempt can be followed by three-phase reclosing, if
selected. At two-phase trip, a failure of a two-phase auto reclosing attempt will inhibit the
auto recloser. No more shots are attempted. If the first trip is a three-phase trip, the auto-
reclosing will be inhibited. No more shots are attempted. The expression "1*2ph" should be
understood as "Only one shot at two-phase auto reclosing".
12.2.2.12
ARMode = 1/2ph + 1*3ph, 1-phase, 2-phase or 3-phase reclosing in the
first shot
At single-phase or two-phase tripping, the operation is as in the example described above,
program mode
three-phase reclosing will follow, if selected. At three-phase trip, a failure of a three-phase
auto reclosing attempt will inhibit the auto recloser. No more shots are attempted. The
expression "1*3ph" should be understood as "Only one shot at three-phase auto reclosing".
ARMode = 1ph + 1*2/3ph, 1-phase, 2-phase or 3-phase reclosing in the
12.2.2.13
first shot
At single-phase or two-phase tripping, the operation is as in the above described example,
program mode
three-phase reclosing will follow, if selected. At two-phase or three-phase trip a failure of a
two-phase or three-phase auto reclosing attempt will inhibit the auto recloser. No more shots
are attempted. The expression "1*2/3ph" should be understood as "Only one shot at two-
phase or three-phase auto reclosing".
Table 41:
MODEINT (integer)
270
1/2/3ph . If the first reclosing shot fails, a three-phase trip will be issued and
1/2/3ph . If the first reclosing shot fails, a three-phase trip will be issued and
Type of reclosing shots at different settings of ARMode or integer inputs to MODEINT
ARMode
1
3ph
2
1/2/3ph
3
1/2ph
4
1ph + 1*2ph
5
1/2ph + 1*3ph
6
1ph + 1*2/3ph
Type of fault
1st shot
1ph
3ph
2ph
3ph
3ph
3ph
1ph
1ph
2ph
2ph
3ph
3ph
1ph
1ph
2ph
2ph
3ph
.....
1ph
1ph
2ph
2ph
3ph
.....
1ph
1ph
2ph
2ph
3ph
3ph
1ph
1ph
2ph
2ph
3ph
3ph
1MRK 505 370-UEN D
M12391-139 v5
GUID-9C2FB801-F324-465E-8FD2-715A9C3D0BD8 v2
M12391-146 v5
2nd-5th shot
3ph
3ph
3ph
3ph
3ph
3ph
3ph
3ph
.....
3ph
.....
.....
3ph
3ph
.....
3ph
.....
.....
Busbar protection REB670