ABB REB670 Series Applications Manual page 254

Table of Contents

Advertisement

Section 11
Secondary system supervision
Harm3Level : This is the set level of 3
DelI> should be modified. Typical setting is 15% of fundamental signal.
the
StValGrad : This setting is used to modify the DelI> based on 3
is 10% to modify the
11.5
Delta supervision of real input DELSPVC
11.5.1
Identification
Function description
Delta supervision of real input
11.5.2
Application
Delta supervision of real input DELSPVC is a general processed input delta supervision. It is
used to configure any processed inputs such as:
Power (S)
Active power (P)
Reactive power (P)
Thermal heat content (ɸ)
Energy
The change over time of these quantities with respect to the old value can be supervised with
this function.
11.5.3
Setting guidelines
Operation : This setting is used to enable/disable the delta supervision function.
MinStVal : The minimum start level of the function. If the input is below this level, the function
will be blocked. It should be set depending on the input connected.
DelSt> : This setting is used to set the start value for delta detection.
DeltaT : This setting defines the number of execution cycles of old data to be used for delta
calculation. That is, if
used to compare the change against.
tHold : This setting defines the pulse length for the start signal. A typical value of this setting is
100 ms.
248
rd
harmonic with respect to fundamental signal at which
DelI> .
IEC 61850
identification
DELSPVC
DeltaT setting is set as 6 for a 3 ms function, an 18 ms old value will be
rd
harmonic level. Typical setting
GUID-470F7470-F3D1-46BC-B0EA-CD180FBA0AB2 v1
GUID-66CFBA71-B3A4-489F-B7F4-F1909B75E1DD v1
IEC 60617
ANSI/IEEE C37.2
identification
device number
GUID-C7F56ACE-D1F2-4F33-96CA-108D7F11FDD5 v1
GUID-0D420893-4266-4EED-8790-1FFA0F41C962 v1
Busbar protection REB670
1MRK 505 370-UEN D
Application manual