ABB REB670 Series Applications Manual page 337

Table of Contents

Advertisement

1MRK 505 370-UEN D
tDelay : The delay between the UP or DOWN activation signal positive front and the output
activation.
StopAtExtremes : Sets the behavior of the switch at the end positions – if set to Disabled , when
pressing UP while on first position, the switch will jump to the last position; when pressing
DOWN at the last position, the switch will jump to the first position; when set to
jump will be allowed.
12.6
Selector mini switch VSGAPC
12.6.1
Identification
Function description
Selector mini switch
12.6.2
Application
Selector mini switch (VSGAPC) function is a multipurpose function used in the configuration
tool in PCM600 for a variety of applications, as a general purpose switch. VSGAPC can be used
for both acquiring an external switch position (through the IPOS1 and the IPOS2 inputs) and
represent it through the single line diagram symbols (or use it in the configuration through the
outputs POS1 and POS2) as well as, a command function (controlled by the PSTO input), giving
switching commands through the CMDPOS12 and CMDPOS21 outputs.
The output POSITION is an integer output, showing the actual position as an integer number 0
– 3, where 0 = MidPos, 1 = Open, 2 = Closed and 3 = Error.
An example where VSGAPC is configured to switch Autorecloser on–off from a button symbol
on the local HMI is shown in figure186. The I and O buttons on the local HMI are normally used
for on–off operations of the circuit breaker.
INTONE
OFF
ON
IEC07000112 V3 EN-US
Figure 186: Control of Autorecloser from local HMI through Selector mini switch
VSGAPC is also provided with IEC 61850 communication so it can be controlled from SA
system as well.
12.6.3
Setting guidelines
Selector mini switch (VSGAPC) function can generate pulsed or steady commands (by setting
Mode parameter). When pulsed commands are generated, the length of the pulse can be
the
Busbar protection REB670
Application manual
IEC 61850
identification
VSGAPC
VSGAPC
PSTO
IPOS1
IPOS2
NAM_POS1
CMDPOS12
NAM_POS2
CMDPOS21
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
43
INVERTER
INPUT
OUT
SMBRREC
ON
SETON
OFF
IEC07000112-3-en.vsd
Section 12
Control
Enabled , no
SEMOD158754-1 v3
SEMOD167850-2 v4
SEMOD158803-5 v9
SEMOD158807-4 v4