Section 12
Control
IED
IEC05000118 V2 EN-US
Figure 144: Application principles for reservation with external wiring
The solution in Figure
application example in Figure 145. The solutions in Figure
same high security compared to the solution in Figure 143, but instead have a higher
availability, since no acknowledgment is required.
IED
. . .
IEC05000178 V3 EN-US
Figure 145: Application principle for an alternative reservation solution
12.3.7
Interaction between modules
A typical bay with apparatus control function consists of a combination of logical nodes or
functions that are described here:
The Switch controller (SCSWI) initializes all operations for one apparatus. It is the
command interface of the apparatus. It includes the position reporting as well as the
control of the position
The Circuit breaker (SXCBR) is the process interface to the circuit breaker for the
apparatus control function.
The Circuit switch (SXSWI) is the process interface to the disconnector or the earthing
switch for the apparatus control function.
The Bay control (QCBAY) fulfils the bay-level functions for the apparatuses, such as
operator place selection and blockings for the complete bay.
The Reservation (QCRSV) deals with the reservation function.
The Protection trip logic (SMPPTRC) connects the "trip" outputs of one or more protection
functions to a common "trip" to be transmitted to SXCBR.
294
BI
BO
144
can also be realized over the station bus according to the
IED
IntlReceive
RESGRANT
IntlReceive
RESGRANT
IED
SCSWI
RES_EXT
SELECTED
Other SCSWI in the bay
BI
SCSWI
RES_EXT
SELECTED
Other SCWI in
the bay
Station bus
1MRK 505 370-UEN D
OR
BO
en05000118.vsd
144
and Figure
145
do not have the
SPGAPC
OR
IN
IEC05000178-3-en.vsd
Busbar protection REB670
Application manual
+
M16626-3 v9