1MRK 505 370-UEN D
Operation of primary apparatuses
Select-Execute principle to give high security
Selection and reservation function to prevent simultaneous operation
Selection and supervision of operator place
Command supervision
Block/deblock of operation
Block/deblock of updating of position indications
Substitution of position indications
Overriding of interlocking functions
Overriding of synchrocheck
Pole discordance supervision
Operation counter
Suppression of mid position
The apparatus control function is realized by means of a number of function blocks
designated:
Switch controller SCSWI
Circuit breaker SXCBR
Circuit switch SXSWI
Bay control QCBAY
Bay reserve QCRSV
Reservation input RESIN
Local remote LOCREM
Local remote control LOCREMCTRL
The signal flow between the function blocks is shown in Figure 138. To realize the reservation
function, the function blocks Reservation input (RESIN) and Bay reserve (QCRSV) also are
included in the apparatus control function. The application description for all these functions
can be found below. The function SCILO in the Figure below is the logical node for interlocking.
When the circuit breaker or switch is located in a breaker IED, two more functions are added:
GOOSE receive for switching device GOOSEXLNRCV
Proxy for signals from switching device via GOOSE XLNPROXY
The extension of the signal flow and the usage of the GOOSE communication are shown in
Figure 139.