Section 16
Ethernet-based communication
in ECT, only filtered for the specific access point. For information on how to activate the
individual communication protocols, see the communication protocol chapters.
The default gateway can be selected by entering the IP address in
gateway is the router that is used to communicate with the devices in the other subnetwork.
By default this is set to
the entered value, but the default gateway has to be in the same subnetwork as the access
point. The default gateway is the router that is being used as default, that is when no route
has been set up for the destination. If communication with a device in another subnetwork is
needed, a route has to be set up. For more information on routes, see the
Technical manual and the Application manual .
the
DHCP can be activated for the front port from the LHMI in Main menu/Configuration/
Communication/Ethernet configuration/Front port/DHCP:1
16.2
Redundant communication
16.2.1
Identification
Function description
IEC 62439-3 Parallel redundancy
protocol
IEC 62439-3 High-availability
seamless redundancy
Access point diagnostic for
redundant Ethernet ports
16.2.2
Application
Dynamic access point diagnostic (RCHLCCH) is used to supervise and assure redundant
Ethernet communication over two channels. This will secure data transfer even though one
communication channel might not be available for some reason
Parallel Redundancy Protocol (PRP) and High-availability Seamless Redundancy (HSR) provides
redundant communication over station bus running the available communication protocols.
The redundant communication uses two Ethernet ports.
388
To increase security it is recommended to uncheck protocols that are not used
on the access point.
0.0.0.0 which means that no default gateway is selected. ECT validates
IEC 61850
identification
PRP
HSR
RCHLCCH
Default gateway . The default
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
-
-
-
-
GUID-172BA5D7-6532-4B0D-8C1D-2E02F70B4FCB v1
Busbar protection REB670
1MRK 505 370-UEN D
Routes chapter in
GUID-B7AE0374-0336-42B8-90AF-3AE1C79A4116 v1
Application manual