ABB REB670 Series Applications Manual page 186

Table of Contents

Advertisement

Section 7
Current protection
tStartTimeout : When one of the two "Follow Modes" is used, there is a settable timer
tStartTimeout which will block the external START input signal when it times-out. This will
automatically also reset the
command. At the same time the STALARM output from the function will have logical value one.
To reset that condition external
prevent unwanted operation of the breaker failure function for cases where a permanent
START signal is given by mistake (e.g.due to a fault in the station battery system). Note that
any backup trip command will inhibit running of
Table 33:
Setting summary for FunctionMode, StartMode, RetripMode and BuTripMode
No.
StartMode
FunctionMode = Current
1
LatchedStart
2
LatchedStart
3
LatchedStart
4
FollowStart
5
FollowStart
6
FollowStart
7
FollowStart&
Mode
8
FollowStart&
Mode
9
FollowStart&
Mode
*) Set level depends on selected BuTripMode, that is, set level can be either IPh> or IN> or both.
180
t1 and t2 timers and consequently prevent any backup trip
RetripMode
t1 and t2 initiated
with
Off
external START
UseFunction
external START
Mode
Always
external START
Off
external START
UseFunction
external START
Mode
Always
external START
Off
external START
and current
above set level
UseFunction
external START
Mode
and current
above set level
Always
external START
and current
above set level
START signal shall be removed. This is done in order to
tStartTimeout timer.
When t1 has
elapsed, TRRET will
never be given
be given if current
is above set level
of IPh>
always be given
never be given
be given if current
is above set level
of IPh>
be given if external
START is present
never be given
be given if current
is above set level
of IPh> and
external START is
present
be given if external
START is present
1MRK 505 370-UEN D
GUID-845257FF-2774-472A-B982-E9DDD8966988 v1
When t2 or t2MPh
t1 and t2 and t2MPh
has elapsed, TRBU
will be stopped
will be given if
(reset) if
current is above
t1 and (t2 or
set level *)
t2MPh) and 150ms
expires and
current is below
set level *)
current is above
t1 and (t2 or
set level *)
t2MPh) and 150ms
expires and
current is below
set level *)
current is above
t1 and (t2 or
set level *)
t2MPh) and 150ms
expires and
current is below
set level *)
current is above
external START
set level *)
disappears
current is above
external START
set level *)
disappears
current is above
external START
set level *)
disappears
current is above
current is below
set level *) and
set level *) or
external START
external START
present
disappears
current is above
current is below
set level *) and
set level *) or
external START
external START
present
disappears
current is above
current is below
set level *) and
set level *) or
external START
external START
present
disappears
Busbar protection REB670
Application manual