ABB REB670 Series Applications Manual page 279

Table of Contents

Advertisement

1MRK 505 370-UEN D
BU-TRIP
ZCVPSOF-TRIP
IEC05000316-WMF V4 EN-US
Figure 133: Lock-out arranged with internal logic with manual closing going through in
12.2.2.20
Evolving fault
An evolving fault starts as a single-phase fault which leads to single-phase tripping and then
the fault spreads to another phase. The second fault is then cleared by three-phase tripping.
The auto recloser will first receive a start signal (
The auto recloser will start a single-phase auto reclosing sequence, if programmed to do so. At
the evolving fault clearance there will be a new
TR3P . The single-phase auto reclosing sequence will then be stopped, and instead the timer, t1
3Ph , for three-phase auto reclosing will be started from zero. The sequence will continue as a
three-phase auto reclosing sequence, if it is a selected alternative reclosing mode. The second
fault which can be single-phase is tripped three-phase because the trip function (SMPPTRC) in
the IED has an evolving fault timer which ensures that the second fault is always tripped three-
phase. For other types of relays where the relays do not include this function, the
output (or the inverted
phase tripping. This signal will, for evolving fault situations, be activated a short time after the
first trip has reset and will thus ensure that new starts (trips) will be three phase.
12.2.2.21
Automatic continuation of the auto reclosing sequence
The auto recloser can be programmed to proceed to the next auto reclosing shots (if multiple
shots are selected) even if start signals are not received from protection functions, but the
circuit breaker is still not closed. This is done by setting
the required delay for the function to proceed without a new start.
12.2.2.22
Thermal overload protection holding the auto recloser back
THOLHOLD input (thermal overload protection holding auto reclosing back) is activated,
If the
it will keep the auto recloser on a hold until it is reset. There may thus be a considerable delay
between start of the auto recloser and the breaker closing command to the circuit breaker. An
external logic limiting the time and sending an inhibit to the
input can also be used to set the auto recloser on hold for a longer or shorter period.
Busbar protection REB670
Application manual
SMBRREC
OR
INHIBIT
UNSUCCL
Functional key,
CCRBRF
RESET LOCK-OUT
SOFTWARE
OR IO RESET
TRBU
MAN CLOSE
OR
SMBRREC CLOSE
SESRSYN
MANENOK
MANSYOK
IED
PERMIT1PH output) is used to prepare the other sub-system for three-
SMPPTRC
OR
SETLKOUT
CLLKOUT
RSTLKOUT
AND
OR
START ) without any three-phase signal ( TR3P ).
START signal and three-phase trip information,
AutoCont = On and tAutoContWait to
SMBO
CLOSE COMMAND
IEC05 000 316-4-en.vsdx
PREP3PH
INHIBIT input can be used. The
Section 12
Control
M12391-217 v4
M12391-223 v5
M12391-226 v3
273