ABB REB670 Series Applications Manual page 367

Table of Contents

Advertisement

1MRK 505 370-UEN D
1.
Set correctly all CT and VT and phase angle reference channel
PCM600 for analog input channels
2.
Connect, in PCM600, measurement function to LV side CT & VT inputs
3.
Set the setting parameters for relevant Measurement function as shown in the following
table 52:
Table 52:
Setting
Operation
PowAmpFact
PowAngComp
Mode
k
UGenZeroDb
IGenZeroDb
UBase (set in
Global base)
IBase (set in
Global base)
SBase (set in
Global base)
Measurement function application for a generator
Single line diagram for this application is given in figure 198.
Busbar protection REB670
Application manual
General settings parameters for the Measurement function
Short description
Off / On
Operation
Amplitude factor to scale
power calculations
Angle compensation for phase
shift between measured I & U
Selection of measured current
and voltage
Low pass filter coefficient for
power measurement, U and I
Zero point clamping in % of
Ubase
Zero point clamping in % of
Ibase
Base setting for voltage level
in kV
Base setting for current level
in A
Base setting for power in MVA
PhaseAngleRef data using
Selected
Comment
value
On
Function must be
1.000
Typically no scaling is required
180.0
Typically no angle compensation is required.
However here the required direction of P & Q
measurement is towards busbar (Not per IED
internal default direction). Therefore angle
compensation have to be used in order to get
measurements in aliment with the required
direction.
L1L2
Only UL1L2 phase-to-phase voltage is
available
0.00
Typically no additional filtering is required
25
Set minimum voltage level to 25%
3
Set minimum current level to 3%
35.00
Set LV side rated phase-to-phase voltage
495
Set transformer LV winding rated current
31.5
Set based on rated power
Section 14
Monitoring
On
SEMOD54481-110 v8
361