ABB REB670 Series Applications Manual page 342

Table of Contents

Advertisement

Section 12
Control
Device 1
IEC04000208 V2 EN-US
Figure 189: Application example showing a logic diagram for control of external devices
12.10.3
Setting guidelines
The parameters for Single command, 16 signals (SINGLECMD) are set via the local HMI or
PCM600.
Parameters to be set are MODE, common for the whole block, and CMDOUTy which includes
the user defined name for each output signal. The MODE input sets the outputs to be one of
the types Off, Steady, or Pulse.
Off, sets all outputs to 0, independent of the values sent from the station level, that is, the
operator station or remote-control gateway.
Steady, sets the outputs to a steady signal 0 or 1, depending on the values sent from the
station level.
Pulse, gives a pulse with 100 ms duration, if a value sent from the station level is changed
from 0 to 1. That means the configured logic connected to the command function block
may not have a cycle time longer than the cycle time for the command function block.
336
Single
command
function
SINGLESMD
CMDOUTy
OUTy
via configuration logic circuits
Configuration logic circuits
&
User-
defined
conditions
1MRK 505 370-UEN D
en04000208.vsd
M12448-3 v2
Busbar protection REB670
Application manual