ABB REB670 Series Applications Manual page 365

Table of Contents

Advertisement

1MRK 505 370-UEN D
Setting
UGenZeroDb
IGenZeroDb
UBase (set in
Global base)
IBase (set in
Global base)
SBase (set in
Global base)
Table 50: Settings parameters for level supervision
Setting
PMin
PMax
PZeroDb
PRepTyp
PDbRepInt
PHiHiLim
PHiLim
PLowLim
PLowLowlLim
PLimHyst
Table 51:
Setting
IAmpComp5
IAmpComp30
IAmpComp100
UAmpComp5
UAmpComp30
UAmpComp100
Table continues on next page
Busbar protection REB670
Application manual
Short Description
Zero point clamping in % of
Ubase
Zero point clamping in % of
Ibase
Base setting for voltage level
in kV
Base setting for current level
in A
Base Setting for power base in
MVA
Short Description
Minimum value
Minimum value
Zero point clamping in 0.001%
of range
Reporting type
Cycl: Report interval (s), Db: In
0.001% of range, Int Db: In
0.001%s
High High limit (physical
value), % of SBase
High limit (physical value), in %
of SBase
Low limit (physical value), in %
of SBase
Low Low limit (physical value),
in % of SBase
Hysteresis value in % of range
(common for all limits)
Settings for calibration parameters
Short Description
Amplitude factor to calibrate
current at 5% of Ir
Amplitude factor to calibrate
current at 30% of Ir
Amplitude factor to calibrate
current at 100% of Ir
Amplitude factor to calibrate
voltage at 5% of Ur
Amplitude factor to calibrate
voltage at 30% of Ur
Amplitude factor to calibrate
voltage at 100% of Ur
Selected
Comments
value
25
Set minimum voltage level to 25%. Voltage
below 25% will force S, P and Q to zero.
3
Set minimum current level to 3%. Current
below 3% will force S, P and Q to zero.
400.00
Set rated OHL phase-to-phase voltage
1000
Set rated primary CT current used for OHL
1000
Set based on rated Power
Selected
Comments
value
-100
Minimum expected load
100
Maximum expected load
3000
Set zero point clamping to 60 MW that is, 3%
of 200 MW
db
Select amplitude deadband supervision
2000
Set ±Δdb=40 MW that is, 2% (larger changes
than 40 MW will be reported)
60
High alarm limit that is, extreme overload
alarm, hence it will be 415 MW.
50
High warning limit that is, overload warning,
hence it will be 371 MW.
-50
Low warning limit -500 MW
-60
Low alarm limit -600 MW
1
Set ±Δ Hysteresis 20 MW that is, 1% of range
(2000 MW)
Selected
Comments
value
0.00
0.00
0.00
0.00
0.00
0.00
Section 14
Monitoring
359