14.2
Gas medium supervision SSIMG
14.2.1
Identification
Function description
Insulation gas monitoring function
14.2.2
Application
Gas medium supervision (SSIMG) is used for monitoring the circuit breaker condition. Proper
arc extinction by the compressed gas in the circuit breaker is very important. When the
pressure becomes too low compared to the required value, the circuit breaker operation shall
be blocked to minimize the risk of internal failure. Binary information based on the gas
pressure in the circuit breaker is used as an input signal to the function. The function
generates alarms based on the received information.
14.2.3
Setting guidelines
The parameters for Gas medium supervision SSIMG can be set via local HMI or Protection and
Control Manager PCM600.
Operation : This is used to disable/enable the operation of gas medium supervision i.e. Off/On.
PresAlmLimit : This is used to set the limit for a pressure alarm condition in the circuit breaker.
PresLOLimit : This is used to set the limit for a pressure lockout condition in the circuit breaker.
Busbar protection REB670
Application manual
General settings parameters for the Measurement function
Short description
Operation Off/On
Amplitude factor to scale
power calculations
Angle compensation for phase
shift between measured I & U
Selection of measured current
and voltage
Low pass filter coefficient for
power measurement, U and I
Zero point clamping in % of
Ubase
Zero point clamping in % of
Ibase
Base setting for voltage level
in kV
Base setting for current level
in A
Selected
Comment
value
On
Function must be
1.000
Typically no scaling is required
0.0
Typically no angle compensation is required.
As well here required direction of P & Q
measurement is towards protected object (as
per IED internal default direction)
Arone
Generator VTs are connected between phases
(V-connected)
0.00
Typically no additional filtering is required
25%
Set minimum voltage level to 25%
3
Set minimum current level to 3%
15,65
Set generator rated phase-to-phase voltage
3690
Set generator rated current
IEC 61850
IEC 60617
identification
identification
SSIMG
-
Section 14
Monitoring
On
GUID-358AD8F8-AE06-4AEA-9969-46E5299D5B4B v3
GUID-AD96C26E-C3E5-4B21-9ED6-12E540954AC3 v4
ANSI/IEEE C37.2
device number
63
GUID-A840E38C-CC42-4995-A569-A6092DDB81B2 v5
GUID-DF6BEC98-F806-41CE-8C29-BEE9C88FC1FD v3