23-01-10 Resolution per revolution

[UDINT, rw]
This object sets the number of distinguishable steps per revolution.
Enabled if = "1".
To avoid counting errors, check that
Allowed values are equal to or lower than value.

23-01-11 Total measuring range

[UDINT, rw]
This parameter sets the number of distinguishable steps over the
total measuring range.
Enabled if = "1".
Allowed values are equal to or lower Total hardware resolution
value.
Example
Multiturn encoder HM5816/16384FB-6 with connection cap "BC-
FDV-C".
Resolution is:
23-01-2A Hardware counts per revolution
23-01-2B Hardware number of turns
 Total hardware resolution:
2048 counts/rev. * 1024 turns are required:
 Enable
23-01-0E Scaling function control
23-01-10 Resolution per revolution
23-01-11 Total measuring range
ATTENTION
To avoid counting errors we recommend values which are power of 2
(2^n: 2, 4,..., 2048, 4096, 8192,...) to be set in
per revolution
and
If
23-01-10 Resolution per revolution
measuring range
attribute should be updated and set according to the new resolution.
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
"
23
-
01
"23
-
01
23-01-11 Total measuring range
values change, then also
AMT58x-DN DeviceNET®
-
2A
"
is an integer value.
-
10"
= 65536 (216)
= 16384 (214)
= 1073741824 (230)
= 01
= 2048 (0000 0800h)
=2048*1024=2097152
(0020 0000h)
23-01-10 Resolution
parameters.
and/or
23-01-11 Total
23-01-13 Preset value
45