17 Data Tx in COS/Cyclic mode

This parameter is meant to set which input data is sent when Change
Of State (COS) / Cyclic mode connection is enabled.
Allowed values: Position value
Position value + velocity

18 Alarm flags

Indicates that a fault occurred and an alarm has been activated, see
11 Supported alarms

19 Delta for COS

When Change Of State .
1 - Cyclic: Slave sends an "I/O message" cyclically. The time
between two subsequent transmissions is set in the
Expected packet rate
"6.5.3 Class 05h: Connection Object").
Change Of State(COS) mode connection is enabled, this parameter
sets the minimum gap between two I/O messages. Values too low
could cause the Bus network to saturate.

20 Auto-save parameters

Yes: when a new parameter is set, the encoder waits 5 seconds and
then saves automatically all new values on EPROM.
No: new parameters are not saved on EPROM automatically. To
save new values Class Instance Editor must be used (default
value; see section "5.4 Save parameter with RSNetWorx).