Fuji Electric FRENIC-HVAC Manual page 124

Hide thumbs Also See for FRENIC-HVAC:
Table of Contents

Advertisement

Three-phase 460 V class series(HP rating)
(001 to 075 HP)
Item
Type
(FRN_ _ _AR1 -4U) (*1)
Nominal applied
Three
motor [HP] (*2)
phase input
(Rated output)
Single
phase input
Three
Rated capacity (kVA)
phase input
(*3)
Rated current (A)
Single
Rated capacity (kVA)
phase input
(*3)
Rated current (A)
Rated voltage (V) (*4)
Overload capability
Three
Main power supply
phase input
(number of phases,
voltage, frequency)
Rated current (A) (*5)
Required power
supply capacity [kVA]
Main power supply
(number of phases,
voltage, frequency)
Single
phase input
Rated current [A] (*5)
Required power
supply capacity [kVA]
Auxiliary control power supply:
(number of phases, voltage,
frequency)
Auxiliary main power supply
(number of phases, voltage,
frequency) (*6)
Voltage, frequency variations
Braking torque [%] (*7)
DC injection braking
EMC filter (IEC/EN 61800-3: 2004) (*8)
DC reactor (DCR) (*8)
Fundamental wave
Power factor
power factor
(at the rated load)
Total power factor
Efficiency (at the rated load) (%)
Applicable (safety) standards
IEC/EN 60529
Enclosure
UL 50
Cooling method
Weight / Mass
IP21
(lbs)
IP55
IP00
Site location
IP00/IP21
Ambient
temperature
IP55
Relative humidity
Atmosphere
Altitude
Atmospheric pressure
Vibration
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
001
002
003
AC460V
1
2
3
motor
-
-
3/4
1.9
3.2
4.3
2.5
4.1
5.5
-
-
1.5
-
-
2
Three-phase, 380 to 480 V (with AVR function)
110%-1 min (Overload interval: Compliant with IEC 61800-2)
Three-phase, 380 to 480 V, 50/60 Hz
1.4
2.7
3.8
1.2
2.2
3.1
Single-phase, 380 to 480 V, 50/60 Hz
-
-
3.8
-
-
1.8
Single-phase, 380 to 480 V, 50/60 Hz
-
Voltage: +10 to -15% (Interphase voltage unbalance : 2% or less) (*9), Frequency: +5 to -5%
20
Braking start frequency: 0.0 to 60.0 Hz; Braking time: 0.0 to 30.0 s; Braking operation level: 0 to 60%
EMC standards compliance : Category C2 (emission) / 2nd Env. (Immunity)
Built-in (IEC/EN 61000-3-2(*10), IEC/EN 61000-3-12)
> 0.98
≥ 0.90
95
96
97
UL 508C, C22.2 No. 14, IEC/EN 61800-5-1:2007, SEMI F47-0706
IP21/IP55 (*11),
UL TYPE 1/ UL TYPE 12
Fan cooling
22
22
22
22
22
22
-
Indoors
14 to 122°F
14 to 104 °F
5 to 95% (No condensation)
The inverter must not be exposed to dust, direct sunlight, corrosive gases, flammable gases, oil mist,
vapor or water drops. Pollution degree 2 (IEC/EN 60664-1) (*12)
The atmosphere can contain a small amount of salt. (0.01 mg/cm
The inverter must not be subjected to sudden changes in temperature that will cause condensation to
form.
3,300 ft max. (*13)
86 to 106 kPa
3mm
2 to less than 9 Hz
2
10 m/s
9 to less than 200 Hz
Specifications
005
007
010
015
020
5
7.5
10
15
20
1.5
3
3
5
7.5
7.1
10
14
19
25
9.0
13.5
18.5
24.5
32
2.3
3.9
5.5
7.1
9.5
3
5
7
9
12
6.5
9.0
12.1
18.0
24.3
5.2
7.2
10
15
20
6.5
9.0
12.1
18.0
24.3
3.0
4.2
5.6
8.3
12
97
97
97
97
97
22
22
22
40
40
22
22
22
40
40
7-7
025
030
040
050
060
25
30
40
50
60
10
10
15
20
25
31
35
47
59
72
39
45
60
75
91
11
13
18
23
27
15
17
23
29
35
Three-phase, 380
to 440 V, 50 Hz
Three-phase, 380
to 480 V, 60 Hz
30..0
35.8
48.5
60.4
72.3
24
29
39
49
58
Single-phase, 380
to 440 V, 50 Hz
Single-phase, 380
to 480 V, 60 Hz
30..0
35.8
48.5
60.4
72.3
14
17
23
28
34
Single-phase, 380
to 440 V, 50 Hz
Single-phase, 380
to 480 V, 60 Hz
10 to 15
98
98
98
98
98
40
40
51
51
110
40
40
51
51
110
2
or less per year)
075
75
30
89
112
34
43
88.7
71
88.7
41
98
110
110