Conformity to the Low Voltage Directive in the EU

If installed according to the guidelines given below, inverters marked with CE are considered as compliant with
the Low Voltage Directive 2006/95/EC.
Compliance with European Standards
Adjustable speed electrical power drive systems (PDS).
Part 5-1: Safety requirements. Electrical, thermal and energy. IEC/EN 61800-5-1: 2007
1. The ground terminal
residual-current-operated protective device (RCD)/earth leakage circuit breaker (ELCB)* as the sole
method of electric shock protection. Be sure to use ground wires of recommended size listed on page vii.
*With overcurrent protection.
2. To prevent the risk of hazardous accidents that could be caused by damage of the inverter, install the
specified fuses in the supply side (primary side) according to the following tables.
- Breaking capacity: Min. 10 kA
- Rated voltage: Min. 500 V
■kW rating
Inverter type
0.75
FRN0.75AR1 -2
1.5
FRN1.5AR1 -2
2.2
FRN2.2AR1 -2
3.7
FRN3.7AR1 -2
(4.0)*
FRN4.0AR1 -2E
5.5
FRN5.5AR1 -2
7.5
FRN7.5AR1 -2
11
FRN11AR1 -2
15
FRN15AR1 -2
18.5
FRN18.5AR1 -2
22
FRN22AR1 -2
30
FRN30AR1 -2
37
FRN37AR1 -2
45
FRN45AR1 -2
55
FRN55AR1S-2
75
FRN75AR1S-2
90
FRN90AR1S-2
* 4.0 kW for the EU. The inverter type is FRN4.0AR1 -2E or FRN4.0AR1 -4E.
Note: A box ( ) replaces an alphabetic letter depending on the enclosure.
A box ( ) replaces an alphabetic letter depending on the shipping destination.
Enclosure: M (IP21) or L (IP55)
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
G should always be connected to the ground. Do not use only a
Fuse rating
(A)
6(IEC/EN 60269-2)
10(IEC/EN 60269-2)
16(IEC/EN 60269-2)
25(IEC/EN 60269-2)
35(IEC/EN 60269-2)
50(IEC/EN 60269-2)
80(IEC/EN 60269-2)
100(IEC/EN 60269-2)
125(IEC/EN 60269-2)
250(IEC 60269-4)
350(IEC 60269-4)
450(IEC 60269-4)
500(IEC 60269-4)
Shipping destination: E (Europe) or A (Asia)
vi
Inverter type
0.75
FRN0.75AR1 -4
1.5
FRN1.5AR1 -4
2.2
FRN2.2AR1 -4
3.7
FRN3.7AR1 -4
FRN4.0AR1 -4E
(4.0)*
5.5
FRN5.5AR1 -4
7.5
FRN7.5AR1 -4
11
FRN11AR1 -4
15
FRN15AR1 -4
18.5
FRN18.5AR1 -4
22
FRN22AR1 -4
30
FRN30AR1 -4
37
FRN37AR1 -4
45
FRN45AR1 -4
55
FRN55AR1 -4
FRN75AR1 -4
75
90
FRN90AR1 -4
110
FRN110AR1S-4
132
FRN132AR1S-4
160
FRN160AR1S-4
FRN200AR1S-4
200
220
FRN220AR1S-4
280
FRN280AR1S-4
315
FRN315AR1S-4
355
FRN355AR1S-4
400
FRN400AR1S-4
500
FRN500AR1S-4
630
FRN630AR1S-4
710
FRN710AR1S-4
Fuse rating
(A)
4(IEC/EN 60269-2)
6(IEC/EN 60269-2)
10(IEC/EN 60269-2)
16(IEC/EN 60269-2)
20(IEC/EN 60269-2)
25(IEC/EN 60269-2)
35(IEC/EN 60269-2)
50(IEC/EN 60269-2)
63(IEC/EN 60269-2)
80(IEC/EN 60269-2)
100(IEC/EN 60269-2)
125(IEC/EN 60269-2)
250(IEC 60269-4)
350(IEC 60269-4)
400 (IEC 60269-4)
450 (IEC 60269-4)
500 (IEC 60269-4)
550 (IEC 60269-4)
630 (IEC 60269-4)
900 (IEC 60269-4)
1250 (IEC 60269-4)
2000 (IEC 60269-4)