Chapter 7
SPECIFICATIONS

7.1 Standard Model

Three-phase 200 V class series (kW rating)
(0.75 to 90kW)
Item
Type
(FRN_ _ _AR1-2) (*1)
Nominal applied motor (kW) (*2)
(Rated output)
Rated capacity (kVA) (*3)
Voltage (V) (*4)
Rated current (A) (*5)
Overload capability
Main power supply (number of
phases, voltage, frequency)
Auxiliary control power supply
(number of phases, voltage,
frequency)
Auxiliary main power supply
(number of phases, voltage,
frequency) (*6)
Allowable voltage/frequency
Rated current (A) (*7)
Required capacity (kVA)
Braking torque [%] (*8)
DC braking
EMC filter (IEC/EN 61800-3: 2004)
DC reactor (DCR) (*9)
Fundamental wave
Power factor
power factor
(at the rated load)
Total power factor
Efficiency (at the rated load) (%)
Applicable (safety) standards
IEC/EN 60529
Enclosure
UL 50
Cooling method
Weight / Mass
IP21
(kg)
IP55
IP00
Site location
IP00/IP21
Ambient
temperature
IP55
Relative humidity
Atmosphere
Altitude
Atmospheric pressure
Vibration
(*1) A box () replaces an alphabetic letter depending on the enclosure. A box () replaces an alphabetic letter depending on the shipping
destination.
Enclosure: M (IP21), L (IP55) or S (IP00)
(*2) Fuji 4-pole standard motor
(*3) Applies to inverters with a rated capacity of 220 V.
(*4) The inverter cannot output a voltage higher than the supply voltage.
(*5) When running the inverter at the carrier frequency 4 kHz or above, it is necessary to derate the current rating.
(*6) If using inverters with DC power input, supply AC power to the internal circuits. Inverters with DC power input are not normally used.
(*7) When the inverter is connected to the power supply of 200 V, 50 Hz, Rsce = 120.
(*8) Indicates average braking torque value for motor alone (varies with motor efficiency).
(*9) Inverters of 45kW or less are equipped with a built-in DC reactor (DCR). An external DCR is provided as standard for inverters of 55kW and
above.
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
0.75 1.5
2.2
3.7
5.5
7.5
(4.0)
(*10)
0.75 1.5
2.2
3.7
5.5
7.5
(4.0)
(*10)
1.9
3.0
4.1
6.8
10
12
3-phase, 200 to 240 V (with AVR function)
5
8
11
18
27
31.8 46.2 59.4 74.8
110%-1 min (Overload interval: Compliant with IEC 61800-2)
3-phase, 200 to 240 V, 50/60 Hz
Single-phase, 200 to 240 V, 50/60 Hz
-
Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less) (*11),
Frequency: +5 to -5%
3.2
6.0
8.6 14.8 20.6 27.8 41.4 55.8 69.0 82.2 112
1.2
2.1
3.0
5.2
7.2
9.7
20
Braking start frequency: 0.0 to 60.0 Hz; Braking time: 0.0 to 30.0 s; Braking operation level: 0 to
60%
EMC standards compliance : Category C2 (emission) / 2nd Env. (Immunity)
Built-in(IEC/EN 61000-3-2, IEC/EN 61000-3-12)
> 0.98
 0.90
97
97
97
97
97
98
UL 508C, C22.2 No. 14, IEC/EN 61800-5-1:2007 , SEMI F47-0706(under application)
IP21/IP55 (*12)
UL TYPE 1/ UL TYPE 12
Fan cooling
10
10
10
10
18
18
10
10
10
10
18
18
Indoors
-10 to +50C
-10 to +40C
5 to 95% (No condensation)
The inverter must not be exposed to dust, direct sunlight, corrosive gases, flammable gases, oil
mist, vapor or water drops. Pollution degree 2 (IEC/EN 60664-1) (*13)
The atmosphere can contain a small amount of salt. (0.01 mg/cm
The inverter must not be subjected to sudden changes in temperature that will cause condensation
to form.
1,000 m max. (*14)
86 to 106 kPa
45 kW or less
3 mm
2 to less than 9 Hz
2
10 m/s
9 to less than 200 Hz
Shipping destination: E (Europe) or, A (Asia)
7-1
Specifications
11
15
18.5
22
30
11
15
18.5
22
30
17
22
28
33
43
3-phase, 200 to 230 V (with AVR function)
88
115
3-phase, 200 to 220 V, 50 Hz
3-phase, 200 to 230 V, 60 Hz
Single-phase, 200 to 230 V, 50/60 Hz
Single -phase, 200 to 220 V, 50 Hz
Single -phase, 200 to 230 V, 60 Hz
15
20
24
29
39
10 to 15
98
98
98
98
98
18
23
23
50
50
18
23
23
50
50
-
55 to 75 kW
3 mm
2 to less than 9 Hz
2
9.8 m/s
9 to less than 20 Hz
2
2 m/s
20 to less than 55 Hz
2
1 m/s
55 to less than 200 Hz
37
45
55
75
90
37
45
55
75
90
55
68
81
107
131
146
180
215
283
346
139
167
203
282
334
49
58
71
98
116
C3/2nd
Standard
accessory
(IEC/EN
61000-3-12)
98
98
98
98
98
IP00
UL open type
70
70
-
70
70
42
43
62
2
or less per year)
90kW
3 mm
2 to less than 9 Hz
2
2 m/s
9 to less than 55 Hz
2
1 m/s
55 to less than 200 Hz