(45 to 710 kW)
Item
Type
(FRN_ _ _AR1 -4 ) (*1)
Nominal applied motor (kW) (*2)
(Rated output)
Rated capacity (kVA) (*3)
Voltage (V) (*4)
Rated current (A) (*5)
Overload capability
Main power supply (number of
phases, voltage, frequency)
Auxiliary control power supply
(number of phases, voltage, frequency)
Auxiliary main power supply
(number of phases, voltage,
frequency) (*6)
Allowable voltage/frequency
Rated current (A) (*7)
Required capacity (kVA)
Braking torque [%] (*8)
DC braking
EMC filter (IEC/EN 61800-3: 2004)
DC reactor (DCR) (*9)
Fundamental wave
Power factor
power factor
(at the rated load)
Total power factor
Efficiency (at the rated load) (%)
Applicable (safety) standards
IEC/EN 60529
Enclosure
UL 50
Cooling method
Weight / Mass
IP21
(kg)
IP55
IP00
Site location
IP00/IP21
Ambient
temperature
IP55
Relative humidity
Atmosphere
Altitude
Atmospheric pressure
Vibration
(*1) A box ( ) replaces an alphabetic letter depending on the enclosure.
A box ( ) replaces an alphabetic letter depending on the shipping destination.
Enclosure: M (IP21), L (IP55) or S (IP00)
(*2) Fuji 4-pole standard motor
(*3) Applies to inverters with a rated capacity of 440 V.
(*4) The inverter cannot output a voltage higher than the supply voltage.
(*5) When running the inverter at the carrier frequency 4 kHz or above (5 kHz or above for inverters of 110 kW or above), it is necessary to
derate the current rating.
(*6) If using inverters with DC power input, supply AC power to the internal circuits. Inverters with DC power input are not normally used.
(*7) When the inverter is connected to the power supply of 400 V, 50 Hz, Rsce = 120.
(*8) Indicates average braking torque value for motor alone (varies with motor efficiency).
(*9) Inverters of 90kW or less are equipped with a built-in DC reactor (DCR). An external DCR is provided as standard for inverters of 110kW
and above.
(*11) Voltage unbalance [%] = (Max. voltage [V] - Min. voltage [V])/Three-phase average voltage [V] x 67 (See IEC/EN 61800-3.)
If this value is 2 to 3%, use an optional AC reactor (ACR).
(*12) IP55 offers protection for short water jets. Do not use outdoors or in places where long-term waterproofing is required.
(*13) Do not install the inverter in an environment where it may be exposed to lint, cotton waste or moist dust or dirt which will clog the heat sink
of the inverter. If the inverter is to be used in such an environment, install it in a dustproof panel of your system.
(*14) If you use the inverter in an altitude above 1000 m, you should apply an output current derating factor as listed in the table below.
Altitude
Output current derating factor
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
45
55
75
90
110
45
55
75
90
110
69
85
114 134
160
3-phase, 380 to 480 V (with AVR function)
91
112 150 176
210
110%-1 min (Overload interval: Compliant with IEC 61800-2)
3-phase, 380 to 440 V, 50 Hz
3-phase, 380 to 480 V, 60 Hz
Single-phase, 380 to 480 V, 50/60 Hz
Single -phase, 380 to 440 V, 50 Hz
Single -phase, 380 to 480 V, 60 Hz
Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less) (*11),
Frequency: +5 to -5%
83.1 102 136 162
201
58
71
95
113
140
10 to 15
Braking start frequency: 0.0 to 60.0 Hz; Braking time: 0.0 to 30.0 s; Braking operation level: 0 to
60%
C2/2nd.
EMC standards compliance : Category C3 (emission) / 2nd Env. (Immunity)
Built-in
(IEC/EN 61000-3-2,
Standard accessory (IEC/EN 61000-3-12)
IEC/EN 61000-3-12)
> 0.98
≥ 0.90
98
98 98
98
98
UL 508C, C22.2 No. 14 , IEC/EN 61800-5-1:2007 , SEMI F47-0706
IP21/IP55 (*12)
IP00
UL open type
UL TYPE 1/ UL TYPE 12
Fan cooling
50
50
70
70
-
50
50
70
70
-
62
Indoors
-10 to +50°C
-10 to +40°C
5 to 95% (No condensation)
The inverter must not be exposed to dust, direct sunlight, corrosive gases, flammable gases, oil mist,
vapor or water drops. Pollution degree 2 (IEC/EN 60664-1) (*13)
The atmosphere can contain a small amount of salt. (0.01 mg/cm
The inverter must not be subjected to sudden changes in temperature that will cause condensation
to form.
1,000 m max. (*14)
86 to 106 kPa
90 kW or less
3 mm
2 to 9 Hz
2
10 m/s
9 to less than 200 Hz
Shipping destination: E (Europe) or A (Asia)
1000 m or lower
1000 to 1500 m
1.00
0.97
7-4
Specifications
132
160
200
220
280
315
132
160
200
220
280
315
192
231
287
316
396
445
253
304
377
415
520
585
238
286
357
390
500
559
165
199
248
271
347
388
98
98
98
98
98
98
64
94
98
129
140
245
110 to 710 kW
3 mm
2 to less than 9 Hz
2
2 m/s
9 to less than 55 Hz
2
1 m/s
55 to less than 200 Hz
1500 to 2000 m
2000 to 2500 m
0.95
0.91
355
400
500
630
710
355
400
500
630
710
495
563
731
891 1044
650
740
960 1170 1370
628
705
881 1115 1256
436
489
611
773
871
98
98
98
98
98
245
245
330
530
530
2
or less per year)
2500 to 3000 m
0.88