Routing Cables From The Bottom - Huawei UPS5000-E User Manual

Hide thumbs Also See for UPS5000-E:
Table of Contents

Advertisement

UPS5000-E-(50 kVA–300 kVA)
User Manual (50 kVA Power Modules)
Step 5 Route the signal cables on the left side of subracks along the left side of the
cabinet and the cables on the right side of subracks along the right side of the
cabinet, and then bind the cables to the cabinet, as shown in
Figure 3-36 Connecting signal cables
----End

3.2.5.2 Routing Cables from the Bottom

Context
● Route cables for the UPS from inside out and from bottom up.
Issue 15 (2022-01-30)
If the mains input and bypass input share a power source, you do not need to
remove the copper bar between the mains and bypass input terminals or
connect the bypass input power cable.
NO TE
The number and colors of signal cables in
NO TICE
Copyright © Huawei Technologies Co., Ltd.
Figure 3-36
are for reference only.
3 Installation
Figure
3-36.
83

Advertisement

Table of Contents
loading

Table of Contents