UPS5000-E-(50 kVA–300 kVA)
User Manual (50 kVA Power Modules)
Step 3 Connect ground cables, as shown in
Figure 3-87 Grounding
Step 4 Route power cables.
Issue 15 (2022-01-30)
NO TE
The quantity of holes in the above figure is for reference only.
If holes are drilled for routing cables, attach grommet strips to the hole edges
to protect cables.
NO TE
: Internal equipotential connection
: Protection ground
Two power sources
Remove the copper bars between the mains and bypass input terminals, as
shown in
Figure
3-88.
Copyright © Huawei Technologies Co., Ltd.
Figure
3-87.
3 Installation
121