Huawei UPS5000-E User Manual page 154

Hide thumbs Also See for UPS5000-E:
Table of Contents

Advertisement

UPS5000-E-(50 kVA–300 kVA)
User Manual (50 kVA Power Modules)
Figure 3-119 Positions for checking foreign matter (UPS5000-E-200K-FM)
(1) Cabinet top
Issue 15 (2022-01-30)
NO TE
1. In the scenarios where holes are drilled for routing cables or covers are removed for
routing cables, after routing cables and checking cable connections, use sealing putty to
fill in the gap between the cables and the cabinet.
2. After verifying the installation, reinstall all the covers.
3. Do not remove the dustproof cover before power-on to prevent dust inside the UPS.
(2) Wiring terminal
blocks
Copyright © Huawei Technologies Co., Ltd.
(3) Switches
3 Installation
(4) Rear of modules
145