System Electrical Specifications - Huawei UPS5000-E User Manual

Hide thumbs Also See for UPS5000-E:
Table of Contents

Advertisement

UPS5000-E-(50 kVA–300 kVA)
User Manual (50 kVA Power Modules)
Item
Overload capability

7.9 System Electrical Specifications

Item
Redundancy design
ECO in a parallel system
Issue 15 (2022-01-30)
Specifications
Inverter overload capability:
● 100% < load ≤ 110%: transfer to bypass mode
● 110% < load ≤ 125%: transfer to bypass mode
● 125% < load ≤ 150%: transfer to bypass mode
● Load > 150% or a short circuit occurs: run for
Bypass overload capability:
● Temperature ≤ 30°C, load ≤ 135%: run for a
● Temperature ≤ 40°C, load ≤ 125%: run for a
● Load > 1000%: run for 100 ms
Specifications
The auxiliary power supplies, centralized
controllers, and parallel signals use redundancy
design.
Supported
Copyright © Huawei Technologies Co., Ltd.
after 60 min or longer
after 10 min (tolerance ± 0.1 min) or longer
after 1 min or longer
200 ms
long time
long time
7 Technical Specifications
190