UPS5000-E-(50 kVA–300 kVA)
User Manual (50 kVA Power Modules)
Figure 3-39 Ground cable connection
Step 4 Route power cables.
●
Issue 15 (2022-01-30)
NO TE
●
: Internal equipotential connection
●
: Protection ground
Two power sources
Remove the copper bars between mains and bypass input terminals.
Figure 3-40
shows power cables routed from the bottom by removing small
covers, as an example.
Copyright © Huawei Technologies Co., Ltd.
3 Installation
86