UPS5000-E-(50 kVA–300 kVA)
User Manual (50 kVA Power Modules)
Figure 4-4 BCB connection setting
----End

4.2 Shutting Down and Powering Off the UPS

Context
After the inverter is shut down, if the bypass is normal, the UPS transfers to
bypass mode; if the bypass is not normal, the UPS supplies no power. Before
shutting down the UPS, ensure that all loads have shut down.
Procedure
Step 1 Shut down the inverter.
Issue 15 (2022-01-30)
NO TICE
On the LCD
On the main menu, choose Common Functions and tap Inv. OFF.
NO TE
You can also tap System Info > Maintenance to shut down the inverter on the
Maintenance screen.
On the WebUI
On the WebUI, choose Monitoring > UPS System > Running Control and
click Inv. OFF. In the displayed dialog box, click OK to shut down the inverter.
On the old WebUI, choose Monitoring > Control and click Inv. OFF. In the
displayed dialog box, click OK to shut down the inverter.
After the inverter shuts down, the UPS works in bypass mode if the bypass is
normal, as shown in
power off if the bypass is abnormal, as shown in
Copyright © Huawei Technologies Co., Ltd.
Figure
4-5. The UPS supplies no power and the loads
4 Operations
Figure
4-6.
156