Huawei UPS5000-E User Manual page 123

Hide thumbs Also See for UPS5000-E:
Table of Contents

Advertisement

UPS5000-E-(50 kVA–300 kVA)
User Manual (50 kVA Power Modules)
Figure 3-77 Drilling holes into the top cover of the cable entry cabinet
Step 11 Determine the cabling mode.
Issue 15 (2022-01-30)
Remove small covers for routing cables
Remove a certain number of small covers from the bottom of the cable entry
cabinet based on the actual cable conditions.
Figure 3-78 Removing small covers
Drilling holes into the large covers for routing cables
a.
Remove all small covers from the bottom of the cable entry cabinet.
b.
Remove the two large covers from the bottom of the cable entry cabinet,
drill holes into them based on site requirements, and install them on the
positions where the small covers were placed.
Copyright © Huawei Technologies Co., Ltd.
3 Installation
114