UPS5000-E-(50 kVA–300 kVA)
User Manual (50 kVA Power Modules)
(3) Bypass input terminals (2L1–2L3, N)
Step 2 Connect the ground cable.
Figure 3-65 Grounding
Step 3 Route power cables.
Issue 15 (2022-01-30)
Two power sources
Remove the copper bar between mains and bypass input terminals.
Figure 3-66 Removing copper bars
Copyright © Huawei Technologies Co., Ltd.
(4) Mains input terminals (1L1–1L3, N)
3 Installation
106