Routing Cables From The Bottom - Huawei UPS5000-E-200K-SM User Manual

50 kva power modules
Hide thumbs Also See for UPS5000-E-200K-SM:
Table of Contents

Advertisement

UPS5000-E-(200 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Figure 3-39 Connecting signal cables
----End

3.2.5.2 Routing Cables from the Bottom

Context
● Route cables for the UPS from inside out and from bottom up.
Procedure
Step 1 Open the front door and remove the cover from the power distribution subrack.
Step 2 Determine the cabling mode.
Issue 17 (2023-07-10)
NO TE
The number and colors of signal cables in
NO TICE
Remove small covers for routing cables.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Figure 3-39
are for reference only.
3 Installation
100