UPS5000-E-(50 kVA–300 kVA)
User Manual (50 kVA Power Modules)
Issue 15 (2022-01-30)
Remove the copper bar between mains and bypass input terminals.
Figure 3-104 Removing copper bars
Figure 3-105 Connecting power cables
Route a neutral wire from the middle of the positive and negative battery
strings.
Take a battery string consisting of 40 batteries as an example. A neutral wire
is routed from the middle of positive and negative battery strings, each
consisting of 20 batteries.